Differential Thermostat Option
If the Chiller is equipped with a DIFFERENTIAL THERMOSTAT, the air probe will need to be located where
ambient temperature is to be monitored. The set-point will be the temperature sensed by this probe. This set-
point can be check by pushing the “SET-POINT” button located on the upper right of the digital display. Releas-
ing this button will display the system water temperature.
Cooling Start-Up
Once flow is established and the thermostat is set to the desired set-point, turn the control power switch to
“ON”. Ensure that the air is flowing in the left side (facing the control panel) and out the right side. If not, reverse
two of the three incoming power supply leads at the terminal strip. Once again, check for correct air flow. All
alarm indicators should be extinguished and the Chiller refrigeration system will cycle in order to maintain the
established set-point.
Re-check the reservoir level to ensure that it is ”FULL” (if so equipped) and add water if necessary.
The Chiller is now ready for normal operation.
TEMP.
HIGHCONTROL
POWER
COOLING
PRESSURE PRESSURE
LOWLOW
POWER
UP
DWN
PUMP
2 & 3
8 & 9
6
5
7
4
1
Control Panel
1. TEMPERATURE INDICATOR/CONTROLLER (Thermostat)- Combines a precise temperature control and
accurate set ability with a convenient LED temperature readout that indicates system liquid temperature.
2. CONTROL POWER SWITCH- A simple (ON/OFF) switch that switches power to the control circuit. This
switch must be “ON” for the Chiller to operate.
3. CONTROL POWER LIGHT- A white light that indicates that Chiller control power is present.
4. COOLING LIGHT- A green light that indicates refrigeration system operation. This light cycles on and off in
response to the thermostat.
5. HIGH PRESSURE ALARM LIGHT- A red light that indicates high refrigeration pressure.
6. LOW PRESSURE ALARM LIGHT- A red light that indicates low refrigeration pressure.
7. LOW TEMPERATURE ALARM LIGHT- A red light that indicates and abnormally low system fluid temper-
ature.
8. PUMP POWER SWITCH (OPTIONAL)- A simple (ON/OFF) switch that switches power to the Chiller
pump. This switch must be “ON” for the Chiller to operate.
9. PUMP POWER LIGHT (OPTIONAL)- A white light that indicates that the Chiller pump power is present.
10. LOW FLOW/HIGH TEMPERATURE INTERLOCK (OPTIONAL)- Contacts are energized when abnormally
low fluid flow or an abnormally high fluid water temperature is sensed by Chiller controls.
11. LOW LEVEL AUDIBLE ALARM (OPTIONAL)- An audible alarm that indicates an unsafe reservoir level.