START UP
WATER FLOW START-UP
Chiller with Pump
It is important to check the pump rotation on the three phase units. Remove the lower side panel to expose the
pump. Turn the pump power switch to the ON position for a few seconds. Observe the motor shaft to ensure
that it is turning in the direction indicated by the arrow located on the pump housing. If the rotation is incorrect,
reverse two of the three incoming power supply leads at the terminal strip. After changing the leads, check the
pump rotation.
NOTE: Running the pump in reverse for more than a few seconds will result in permanent
pump damage.
After ensuring that the system piping is free from obstruction and that all valves are open, turn the pump power
switch to the ON position. The pump power indicator should illuminate, indicating that the pump is operating.
All Chillers with pumps are provided with a pressure regulating valve on the pump discharge. This valve is pre-
set at the factory to ensure that system pressure does not exceed the capabilities of the pump motor and/or pip-
ing. If this valve requires adjustment, please contact the factory for proper setting procedure and pressures.
A flow meter and throttling valve can be added in the chiller inlet line in order to monitor and/or adjust the flow
rate through the Chiller.
Once the flow has been established, the thermostat can be adjusted to the desired set-point.
Chiller without Pump
A flow meter and throttling valve can be added in the Chiller inlet line in order to monitor and/or adjust the flow
rate through the Chiller.
Once the flow has been established, the thermostat can be adjusted to the desired set-point. See thermostat
adjustment.
THERMOSTAT ADJUSTMENT
Standard Thermostat
The following procedure should be followed to adjust the standard thermostat:
1. Push the SET button located to the right of the digital display. The current set-point will be displayed.
2. While holding the SET button, push the UP or DOWN button until the desired set-point is displayed.
3. Release SET button. The display will show the system water temperature. The set-point can be viewed at
any time by pressing the SET button.
The thermostat has a range that has been preset at the factory. The range is 40F (5C) to 100F (38C). If
operation outside of this range is required, please contact the Remcor Technical Service Department.
UP
DOWN SET