CLASSIC 1000
REMOTE COOLER
4
3. WATER COOLED MODEL
INSTALLATION INSTRUCTIONS
3.1 SITING
SIDE VIEW
Install on
firm level
surface
100mm (minimum) clearance
required to allow adequate ventilation
2.0m max
PLAN
13A Socket
Castors allow
movement in
any direction
Minimum bend radius
of 100mm
Do not insulate
pipework
No contact
between
pipes
Discharge
Unit
Remote
Cellar
Push in
fittings
3.2 SITING & INSTALLATION DIAGRAM
GENERAL (Applies to both base and discharge unit)
1. Prevent exposure to water spillage, spray or very high
humidity.
2. Never allow air vents (louvres) to become obstructed
or blocked.
3. Protect from physical damage and do not place heavy
items on top.
BASE UNIT
1. Do not drag over rough floors or down steps and
always keep in an upright position.
2. Site as near to the stored product as possible.
3. Allow access to side and front panels, for maintenance
and servicing.
4. Locate the Classic 1000 within 2m of a grounded,
switched, 13 amp, 230v socket which is easily
accessible for isolation of the cooler. The socket
should be installed to current IEE regulations.
It is recommended that the mains electrical supply is
protected by RCCB.
The Cooler must be earthed.
DISCHARGE UNIT
1. The Discharge Unit should be mounted in a convenient
position on an EXTERIOR wall and provide access
for pipes and electrical cable to the Base Unit
(Maximum 30m run length from Base Unit). If no
exterior wall is available within 30 metres of the Base
Unit, then mount inside on a wall in a cool room with
plenty of fresh air ventilation. Avoid warm areas (i.e.
cupboards or small storerooms).
2. The Discharge Unit is designed to operate in the range
of ambient temperatures from
-10°C to 35°C.